The following four pictures were taken 1-10-2021 at 3 PM, showing a 3 inch snowfall on the family farm here in central Texas. This was big snowflake stuff, with the wetness and cohesion to make good snowballs.
Figure 1 -- Out front door,
looking a bit leftward
Figure 2 -- Out front door,
looking a bit rightward
Figure 3 -- Out the dining room window into the back yard, looking a bit leftward
Figure 4 -- Out the dining room window into the back yard, looking a bit rightward
On the average, we near
Waco, Texas, get around 1 significant icing event per
winter. This winter has been very different: first a real snow storm in January, then shortly after in February, a big polar vortex failure brought us 3
events in rapid succession, starting with
an ice storm 2-11-2021, then another
snow storm 2-14-2021, then yet another
ice storm 2-17-2021.
Figure 5 -- Out the front door and leftward, ice storm event 2-11-21 that closed roads
Figure 6 -- Out the front door slightly rightward, ice storm event 2-11-21
Figure 7 -- Out the front door strongly rightward, ice storm event 2-11-21
Figure 8 -- Ice only partly melted Sat 2-13-21 from the
Thursday ice storm event
There was no big thaw after this ice storm; temperatures remained continuously below
freezing. The previous snow was big
flakes. The next was fine powder rarely
seen in Teas at all. It fell atop the
unmelted ice from the ice storm.
Temperatures started out in the 20’s for this snow, falling rapidly into the teens by dark.
Figure 9 -- Sun 2-14-21 Valentine’s Day snow begins on top
of unmelted ice
We got about 3 inches of powder snow from this event. Then it turned very cold indeed, almost setting all-time records. Monday 15th was clear and
cold, with a morning low near 4 F. Tuesday 16th was clear but cold (about
0 F AM then stayed in the 20’s PM; Waco
Regional airport recorded -1 F for the low).
We had been continuously below freezing around the clock for some 5 days
by this time.
Figure 10 -- Mon 2-15-21: 3 inches of very fine powder-type
snow covers the ice
We got hit with another ice storm Tuesday night into
Wednesday 17th. This was not a lot of
ice, but it formed a crust atop the 3
inches of powder snow. Temperatures did
not get above freezing until Friday afternoon 2-19-21 (9 days continuously
below freezing, unprecedented in Texas).
Figure 11 -- Wednesday 2-17-21: Results of ice storm on top of unmelted snow
The January snow was one weather system, and the 3 February events (ice/snow/ice) were
one “polar vortex” failure with 3 small systems sweeping across it. We in Texas set historic records for snowfall
and cold during the two systems (4 events in all). That includes the unprecedented 9 days
continuously below freezing, around the
clock.
Many people suffered disastrous and expensive failures
because of the sustained cold and the widespread blackouts. We out here on the farm did not, fortunately.
The slick roads caused major problems, and loss of life as well. Having spent two record-setting winters in
Minnesota a quarter century ago, I had
no troubles with the cold or the roads. (But
I learned how to drive on this stuff in the school of hard knocks, long before ever going to Minnesota. That’s another story for some other time.)
The long-duration sustained cold is the real reason
why the Texas energy grid came very near to total collapse, with people dying or near-fatally endangered
in the cold without power. Many
of the natural gas plants went off-line for lack of fuel, because the gas well infrastructure and
transmission pipelines were not robust enough to resist the sustained and very
severe cold. There may or may not have been
troubles at coal plants, that seems not
to be very clear in most of the news reports.
But natural gas dominates Texas generation, with coal second, wind third,
and then nuclear. One nuclear plant
had one unit shut down for a bad sensor.
There were several “frozen” wind turbines that went off line (whatever
“frozen” actually means), but ERCOT’s
own data says the wind farms were still producing about twice what was actually
expected of them this time of year. The
bulk of the problem was fuel delivery interruptions at the gas plants that are
the bulk of the Texas generating capacity,
pure and simple.
ERCOT did not cause this crisis with its rolling
blackouts, but nothing ERCOT can do could
fix it, either! Simply put,
the return of warmer weather,
allowing gas production and transmission to resume, was what corrected it. The problem was one of management at
many levels (not just ERCOT) not learning the lessons of prior cold
weather experience here in Texas, and
elsewhere.
We here in Texas have had grid capacity troubles with polar
vortex events at least once before, and
other grids in colder parts of the country also have good lessons to teach
about cold weather operation. Baldly
stated, ERCOT, the big utilities, and the Texas government chose not to
learn those lessons to reduce expenses!
Which is really why we have had a disaster, that killed and threatened people.
Meanwhile, there is a
photo/video that has gone viral, claimed
to be of a helicopter spraying de-icing fluid on a frozen Texas windmill
generator. Except that it is not
a Texas windmill! Both Reuters and
Associated Press (and many others) have debunked this claim. The photo is really of a Swedish windmill
being deiced, during the winter of
2014-2015, some 6 years ago. Plus,
the “deicing fluid” is simple hot water,
although it is heated with an oil burner (you simply use what you have
at hand, to get the job done).
Figure 12 -- This was the viral photo falsely claimed to be
a frozen Texas wind generator
Based on what I have seen from multiple sources, about half the windmills in the west Texas
wind farms were indeed shut down for cold weather problems. Even so,
according to ERCOT’s own data,
the remainder was generating about twice what ERCOT expected from the
wind farms. But even if all of them had
been generating, it wouldn’t have been
enough: wind is but 20-25% of Texas’s
capacity. We were short more than
30% of Texas’s generating capacity.
The real problem is that over half our Texas
generating capacity is natural gas plants,
and about half of those got shut down for lack of fuel. When you add in a few coal plants that had
cooling water lines break in the cold,
and one nuclear unit shut down for a bad sensor, plus some windmills frozen, you get exactly what we saw happen!
This could not correct itself until the frozen well heads
and transmission pipelines unfroze. That
simply required warmer temperatures. It
will happen again next time the polar vortex fails in a big way like this, unless “we” harden the natural gas system
against long-duration cold weather.
That technology is well-known,
but was NOT required in Texas. In
hindsight, it should have been required.
There were and still are two fundamental changes
needed for the way Texas manages its electric grid. One is to add an incentive for the addition
of generating capacity, not just the
sale of electricity from existing capacity.
That would also help with the perennial summer capacity vs demand
troubles, as well. The second is far more important: make the voluntary best practices for
cold weather robustness into mandatory regulatory requirements. Had that already been in place, the 2021 polar vortex event would very likely
not have been the disaster that it was!
I suggest very strongly that you consider that ugly little
fact, before re-electing the same
politicians that let this happen to you.
Update 2-21-21:
Much of the ice had melted during the Friday afternoon (2-19-21) above freezing. Most of the remaining ice melted during Saturday and Saturday night, both above freezing. Today (Sunday) things look normal again, only traces remain.
What's all over the media are the CYA ("cover your ass") lies about who is responsible for the cold weather grid disaster. There are those who persist in trying to pin the blame on the wind farms, even though the truth about the real problem has already been exposed. And that is exactly what I described in the article: frozen natural gas supply sources and transmission lines account for at least 30% of the 40% of Texas's generating capacity that shut down, for lack of fuel.
That's the proximate cause of the grid disaster, but ultimately the source of this traces to improper regulatory requirements management by the state government. And by "government", I mean ERCOT, the PUC, the governor's office, and the legislature. Plenty of blame to go around.
The free market is the most powerful engine of creation yet devised by humans, but it devolves into piracy and slavery if there are no enforced rules to constrain it to serve the public interest. We humans have known that for some millennia now, political lies and ideology favoring an absolutely-unregulated market notwithstanding.
You are already seeing hints of the piracy aspect in the price-gouging on utility bills and for natural gas prices. There will be more. That money is going into executive's pockets, not into correcting the problems we faced. You are also seeing it in the arguments over exactly who is going to pay for all the plumbing and water damage caused by the extended power outages. And nobody has yet brought up responsibility for the lives lost and injuries suffered.
I suggest you remember this disaster next election. The politicians you have been re-electing, and their appointees, are the ones who ultimately caused this. It should be painfully apparent to anyone, that it is way past time to try somebody else for a while.
Update 3-3-2021:
It's not quite 2 weeks since the ice from the awful storm melted. Here is a view of my front yard, showing the green in the ground cover. Spring is here! (Although it frosted this morning, too!).